Items | Specifications |
Number of Outputs Points | 8 |
Common | 8 points 2 common x 1 |
Output Voltage Range | 5 to 30 V DC/5 to 240 V AC |
Output Type | Relay a-contact (SPST) |
Peak Voltage | 30 V DC, 264 V AC |
AC Frequency | 47 to 60 Hz |
ON-time Voltage Drop | Not applicable |
Maximum Load Current | 1 A/point, 4 A/common |
Maximum Leakage Current | 0.1 mA (265 V AC) |
Maximum Allowable Inrush Current |
Output: 3 A (10 ms) Common: 10 A (10 ms) |
Minimum Load Current | 5 mA (5 V DC) |
OFF→ON Response Time | 12 ms |
ON→OFF Response Time | 10 ms |
Terminal Type | Removable 10P terminal block |
Status Display | Logic side |
Fuse | 6.3 A slow-blow fuse 1 unit (D2-FUSE-3 (Z-6FK)) |
Weight | 110 g |